7. In terms of Rules 48 of Public Procurement Rules, 2004 Grievance Redressal Committee (GRC) is notified for the subject procurement and notification copy is available on the procuring agency’s website and also available on EPADS v2.0 as well as Authority’s website at (www.ppra.org.pk).
PMU (FESCO) (Faisalabad Electric Supply Company (FESCO)), Chief Engineer
Chief Engineer (Development), FESCO Head Office, Canal Road, Faisalabad, Pakistan., Faisalabad City, Faisalabad (District), Faisalabad Division (Division), Punjab (Province).
+92-370-180-0102
muhammad.waqasbaig@fesco.com.pk
The following specific data for the procurement of Non-Consultancy Services to be procured shall complement, supplement, or amend the provisions in the Instructions to Bidders (ITB). Whenever there is a conflict, the provisions herein shall prevail over those in ITB.
BDS Clause Number
ITB Number
Amendments of, and Supplements to, Clauses in the Instruction to Bidders
BDS Clause Number 1
Name of Procuring Agency: PMU (FESCO) (Faisalabad Electric Supply Company (FESCO))
The subject of procurement is: TENDER NO.NCB-881/FESCO/PMU/GSO/2026-27 FOR REPAIR OF 132/11.5KV, 31.5/40MVA POWER TRANSFORMERS, 132/11.5KV, 20/26MVA POWER TRANSFORMERS, 132/11.5KV, 10/13MVA POWER TRANSFORMERS AND 66/11KV, 15/18MVA POWER TRANSFORMERS
Expected commencement date: Saturday, April 24, 2027
BDS Clause Number 2
Financial year for the operations of the Procuring Agency: 2026-27
Name and identification number of the Contract: P145176
BDS Clause Number 3
JV/Consortium or Association Allowed: No
Number of JV/Consortium Members: Nil
BDS Clause Number 4
The Bidders may seek clarifications through EPADS v2.0: Clarification Date: Saturday, October 24, 2026
BDS Clause Number 5
Any addendum, in case issued, shall be published on PMU (FESCO) (Faisalabad Electric Supply Company (FESCO)) website and on EPADS v2.0.
BDS Clause Number 6
List of documents required along with the bid: No
BDS Clause Number 7
The qualification criteria to establish the supply / production capability of the bidder.
see Eligibility Criteria
BDS Clause Number 8
Services and Their related documents:
See section Required Services and Scope of Work
BDS Clause Number 9
Price schedule will be provided according to the format defined and acquired.
see section price schedule.
BDS Clause Number 10
Specifications:
see section of specifications.
BDS Clause Number 11
The price shall be Fixed.
BDS Clause Number 12
Currency of the Bids shall be : PKR
BDS Clause Number 13
The Bids/Bid Validity period shall be: 120 Days
BDS Clause Number 14
The amount of Bid Security shall be as defined in Bid Security Section for items and lots given in BDS 6
The Bid Security shall be in the form of: Pay Order, Banker's Cheque, Call at Deposit, Bank Guarantee, Demand Draft
BDS Clause Number 15
The Bids security shall be valid for twenty-eight (28) days beyond the expiry of the Bids validity period specified in the bidding documents, for example the bid validity is 90 days so the bid security shall be valid for 90+28 = 118 days.
BDS Clause Number 16
Alternative Bids to the requirements of the bidding documents will not be permitted.
BDS Clause Number 17
Bid shall be submitted online on EPADS v2.0 whereas hard copy of the bid security should be submitted to the following;
Chief Engineer (Development), FESCO Head Office, Canal Road, Faisalabad, Pakistan., Faisalabad City, Faisalabad (District), Faisalabad Division (Division), Punjab (Province).
Bids that are not submitted on EPADS v2.0 shall be disqualified.
The deadline for Bids submission is: Tuesday, October 27, 2026 11:00 AM
BDS Clause Number 18
The Bids opening shall take place on EPADS v2.0.
Day : Tuesday
Date: Tuesday, October 27, 2026
Time : 11:30 AM
BDS Clause Number 19
Selection technique adopted will be: Least Cost Based Selection (LCBS)
see Evaluation Criteria
BDS Clause Number 20
The Performance guarantee shall: 5.00%.
The Performance Guarantee shall be acceptable in the form of: Bank Guarantee
21.
51.1
Arbitrator shall be appointed by mutual consent of the both parties.
BDS Clause Number 22
Grievence against this procurement shall be submitted online on EPADS v2.0.
| Bidder's Type | Required Registration |
|---|---|
|
Individual / Individual Consultant Sole Proprietorship Partnership Firm Company (Private Limited) Company (Public Limited) Company (Holding Company) Company (Limited by Guarantee) State Owned Enterprise (Private Limited) State Owned Enterprise (Public Limited) |
NADRA CITIZENSHIP (CNIC/NICOP) FBR (NTN) FBR (GSTN) |
| Eligibility Criteria | Document |
|---|---|
| The Bidder shall submit the certificate that the General Conditions of Contract for Purchase by WAPDA Dated: 12.08.1984 amended to-date, Registration Procedure, PEPCO procurement guidelines/ instructions & PPRA Rules 2004 are acceptable to the bidder and are hereby agreed to by the bidder.. | Yes |
| Bidder shall submit bid Security of an amount not less than as calculated/mentioned in E-PAD Portal against each tender. The Bid Security shall be denominated in the currencies of the bid (i.e. PKR). Moreover, the copy of bid security must be submitted online and Original Bid Security shall be submitted in the O/O Chief Engineer (Development) PMU FESCO at the time of bid. Lesser bid security amount or validity of bid security will lead to rejection of bid. | Yes |
| The bidder shall submit the under-taking/declaration certificate for the use of prime material that the material used for the repairing of 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will 100% conform the WAPDA/NTDC/PEPCO Specifications No. P-46:2008. | Yes |
| The bidder shall submit the under-taking/declaration certificate that Firm is not involved in using or used material since five years or since (Number of years since in 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer repairing/ manufacturing business). | Yes |
| Bidder shall submit the certificate that the firm is not involved in any litigation with any formation of WAPDA/ DISCOs/ GENCO's/ NTDC. | Yes |
| Bidder shall submit a certificate that the firm is not black listed/debarred from WAPDA/DISCO’s/GENCO’s/NTDC at present. | Yes |
| The bidder should have sound financial status. In order to determine the same the bidder shall provide its up to date financial statements i.e audited balance sheet, income statement, and cash flow statements for the last 3 years (three years). The bidders net worth calculated as a difference between total assets and total liabilities must be positive for the last 3 years. In this context the bidder is required to submit the same with the bid. | Yes |
Least Cost Based Selection (LCBS)
Weightage
| Technical Evaluation % |
|---|
| 100 |
| Technical Marks | 100 | |
|---|---|---|
| Passing Marks | 100 | |
| Formation Experience. | ||
| Concerned Formation Experience in this Field must be 03 years minimum. (Quantitative)(Doc Required) | 30 | |
| Contractual experience | ||
| At least four (04) numbers power transformers successfully already repaired by the contractor. (Quantitative)(Doc Required) | 40 | |
| Satisfactory Performance | ||
| Satisfactory Performance Certificate must be submitted by the bidder in last 03-years (Quantitative)(Doc Required) | 30 | |
Lot Title : LOT II
Bid Security : 1400000 PKR
| Position | Delivery Schedule | Quantity |
|---|---|---|
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Nishatabad New (Make: ELTA) | Address: T-2 at 132KV G/S Nishatabad New (Make: ELTA) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-4 at 132KV G/S Tandlianwala (Make: ELTA) | Address: T-4 at 132KV G/S Tandlianwala (Make: ELTA) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-1 at 132KV G/S Khewa (Make: GANZ) | Address: T-1 at 132KV G/S Khewa (Make: GANZ) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Sammundri (Make: ELTA) | Address: T-2 at 132KV G/S Sammundri (Make: ELTA) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Bhagtanwala (Make: ELECTROPUTER) | Address: T-2 at 132KV G/S Bhagtanwala (Make: ELECTROPUTER) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-1 at 132KV G/S Bhabra (Make: ELECTROPUTER) | Address: T-1 at 132KV G/S Bhabra (Make: ELECTROPUTER) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Quaidabad (Make: SHENYANG) | Address: T-2 at 132KV G/S Quaidabad (Make: SHENYANG) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
Lot Title : LOT I
Bid Security : 1000000 PKR
| Position | Delivery Schedule | Quantity |
|---|---|---|
| Repair of 132/11.5KV, 31.5/40MVA Power Transformers, T-2 at 132KV G/S Sargodha City (Make: Siemens) | Address: T-2 at 132KV G/S Sargodha City (Make: Siemens) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
| Repair of 132/11.5KV, 31.5/40MVA Power Transformers, T-1 at 132KV G/S Quaidabad (Make: ELTA) | Address: T-1 at 132KV G/S Quaidabad (Make: ELTA) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
| Repair of 132/11KV, 10/13MVA Power Transformers, T-3 at 132KV G/S Small Industrial Estate (Make: GANZ) | Address: T-3 at 132KV G/S Small Industrial Estate (Make: GANZ) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
| Repair of 132/11KV, 10/13MVA Power Transformers, T-1 at 132KV G/S Chhina (Make: ELPROM) | Address: T-1 at 132KV G/S Chhina (Make: ELPROM) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
| Repair of 66/11KV, 15/18MVA Power Transformer, T-1 at 66KV G/S Makarwal (Make: GANZ) | Address: T-1 at 66KV G/S Makarwal (Make: GANZ) Schedule: 48 Hours from the start of ShutdownQuantity: 01/Qty |
1/Qty |
Yes
LOT II
| Position | Related Services |
|---|---|
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Nishatabad New (Make: ELTA) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-4 at 132KV G/S Tandlianwala (Make: ELTA) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-1 at 132KV G/S Khewa (Make: GANZ) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Sammundri (Make: ELTA) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Bhagtanwala (Make: ELECTROPUTER) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-1 at 132KV G/S Bhabra (Make: ELECTROPUTER) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
| Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Quaidabad (Make: SHENYANG) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
LOT I
| Position | Related Services |
|---|---|
| Repair of 132/11.5KV, 31.5/40MVA Power Transformers, T-2 at 132KV G/S Sargodha City (Make: Siemens) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
| Repair of 132/11.5KV, 31.5/40MVA Power Transformers, T-1 at 132KV G/S Quaidabad (Make: ELTA) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
| Repair of 132/11KV, 10/13MVA Power Transformers, T-3 at 132KV G/S Small Industrial Estate (Make: GANZ) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
| Repair of 132/11KV, 10/13MVA Power Transformers, T-1 at 132KV G/S Chhina (Make: ELPROM) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
| Repair of 66/11KV, 15/18MVA Power Transformer, T-1 at 66KV G/S Makarwal (Make: GANZ) | All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008. |
Lot Title : LOT II
Position: Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Nishatabad New (Make: ELTA)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.Position: Repair of 132/11.5KV, 20/26MVA Power Transformers, T-4 at 132KV G/S Tandlianwala (Make: ELTA)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.Position: Repair of 132/11.5KV, 20/26MVA Power Transformers, T-1 at 132KV G/S Khewa (Make: GANZ)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.Position: Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Sammundri (Make: ELTA)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.Position: Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Bhagtanwala (Make: ELECTROPUTER)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.Position: Repair of 132/11.5KV, 20/26MVA Power Transformers, T-1 at 132KV G/S Bhabra (Make: ELECTROPUTER)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.Position: Repair of 132/11.5KV, 20/26MVA Power Transformers, T-2 at 132KV G/S Quaidabad (Make: SHENYANG)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.Lot Title : LOT I
Position: Repair of 132/11.5KV, 31.5/40MVA Power Transformers, T-2 at 132KV G/S Sargodha City (Make: Siemens)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.Position: Repair of 132/11.5KV, 31.5/40MVA Power Transformers, T-1 at 132KV G/S Quaidabad (Make: ELTA)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.Position: Repair of 132/11KV, 10/13MVA Power Transformers, T-3 at 132KV G/S Small Industrial Estate (Make: GANZ)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.Position: Repair of 132/11KV, 10/13MVA Power Transformers, T-1 at 132KV G/S Chhina (Make: ELPROM)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.Position: Repair of 66/11KV, 15/18MVA Power Transformer, T-1 at 66KV G/S Makarwal (Make: GANZ)
Specifications / Requirements:
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement. 1) On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer. 2) Oil Drain Out/Refill will be responsibility of bidder. 3) Sealant should be able to Withstand Temperature upto 100 C. 4) Sealant / Putty should be non reactive with Transformer Oil. 5) Sealant / Putty should be non conductive UV Resistant. 6) Maximum Time for curing and energizing should be less than 48 hours. 7) Insulation Tests (IR and C&DF) before and after leakage repair activity. 8) Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors. 9) Transportation of expert team at site will be responsibility of concerned contractor/supplier. 10) During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges. 11) The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008. 12) All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement.
1)Â Â Â On site Oil Leakage repair from the prime parts of the power transformers to be attended include Main Gas Ket, Flange Valves of Radiator Tubes, LT Bushes, Tap Changer.
2)Â Â Â Oil Drain Out/Refill will be responsibility of bidder.
3)Â Â Â Sealant should be able to Withstand Temperature upto 100 C.
4)Â Â Â Sealant / Putty should be non reactive with Transformer Oil.
5)Â Â Â Sealant / Putty should be non conductive UV Resistant.
6)Â Â Â Maximum Time for curing and energizing should be less than 48 hours.
7)Â Â Â Insulation Tests (IR and C&DF) before and after leakage repair activity.
8)Â Â Â Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors.
9)Â Â Â Transportation of expert team at site will be responsibility of concerned contractor/supplier.
10)Â During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges.
11)Â The 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer shall conform to WAPDA/NTDC/PEPCO Specification No. P-46:2008.
12)Â All material 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer will be used as per specification No.P-46:2008.
For Individual Positions
| # | Position Title | Quantity | Unit Price (PKR) | Total Price (PKR) | Delivery Location | Delivery Period / Year | Country of Origin |
|---|---|---|---|---|---|---|---|
| 1 | |||||||
| 2 |
| # | Lot Title | Total Lot Price (PKR) | Country of Origin |
|---|---|---|---|
| 1 | [Lot 1 Title] |
The following Special Conditions of Contract shall supplement the General Conditions of Contract. Whenever there is a conflict, the provisions herein shall prevail over those in the Conditions of Contract. The corresponding clause number of the GCC is indicated in parentheses.
Number of GC Clause
Amendments of, and Supplements to, Clauses in the General Conditions of Contract
Definitions
The Procuring Agency is: PMU (FESCO) (Faisalabad Electric Supply Company (FESCO)), Chief Engineer Chief Engineer (Development), FESCO Head Office, Canal Road, Faisalabad, Pakistan., Faisalabad City, Faisalabad (District), Faisalabad Division (Division), Punjab (Province).
The Supplier is:
The title of the subject procurement is:TENDER NO.NCB-881/FESCO/PMU/GSO/2026-27 FOR REPAIR OF 132/11.5KV, 31.5/40MVA POWER TRANSFORMERS, 132/11.5KV, 20/26MVA POWER TRANSFORMERS, 132/11.5KV, 10/13MVA POWER TRANSFORMERS AND 66/11KV, 15/18MVA POWER TRANSFORMERS
Number of GC Clause 2
Applicable/Governing Law:
The Contract shall be interpreted in accordance with the laws of Islamic Republic of Pakistan
Number of GC Clause 3
Language:
The language of the Contract, all correspondence and communications to be given, and all other documentation to be prepared and supplied under the Contract shall be in English.
Number of GC Clause 4
Notices:
The addresses for the notices are:
Procuring Agency:
PMU (FESCO) (Faisalabad Electric Supply Company (FESCO)), Chief Engineer
Chief Engineer (Development), FESCO Head Office, Canal Road, Faisalabad, Pakistan., Faisalabad City, Faisalabad (District), Faisalabad Division (Division), Punjab (Province).
+92-370-180-0102
muhammad.waqasbaig@fesco.com.pk
Contractor/ Bidder:
[Name, address and telephone number].
The Contractor/ Bidder’s Representative(s)
[Name, address, telephone number and e-mail address]
Number of GC Clause 6.1
The Authorized Representatives are:
For the Procuring Agency:
PMU (FESCO) (Faisalabad Electric Supply Company (FESCO)), Chief Engineer
Chief Engineer (Development), FESCO Head Office, Canal Road, Faisalabad, Pakistan., Faisalabad City, Faisalabad (District), Faisalabad Division (Division), Punjab (Province).
+92-370-180-0102
muhammad.waqasbaig@fesco.com.pk
For the Bidder:
Name: ………………………
Designation: ……………..
Address: ……………………………..
Number of GC Clause 7
Effectiveness of the contract
The Contractor/Bidder shall be effective within ….. days from the date of signature of the Contract by both parties
Number of GC Clause 8
Commencement of Contract:
The Contractor/ Bidder shall provide Non-Consultancy Services from the effective date of contract.
Number of GC Clause 10.2
Expiration of Contract:
The time period shall be ………………….
Number of GC Clause 14
Termination
In the event of termination of the contract due to any reason as already defined in the General Conditions of Contract, the Bidder shall be responsible for providing to the Authority the Services till the time of alternate arrangements.
Number of GC Clause 16
Conflict of Interest:
The Procuring Agency reserves the right to determine on a case-by-case basis whether the Bidder should be disqualified from providing services due to a conflict of a nature described in Clause GCC C2.
Number of GC Clause 20
Liquidated Damages
If the Bidder fails to provide services as required under the contract or in case of any data loss/data breach or any incident compromising the data security or other such failures related to any services, the Bidder shall pay to the Procuring Agency as Liquidated Damages at a rate of 1.00% to 10.00% of the Contract value, in accordance with the extent of performance failure & the cost of investigating such incidents as judged by the Authority.
Number of GC Clause 21
Performance Guarantee:
The amount of performance guarantee shall be 5.00% of the contract price in acceptable form of Bank Guarantee
Number of GC Clause 27
Currency of Payment:
All the payment to be released to the contractor/Bidder shall be in Pakistani Rupees.
Number of GC Clause F
Payment terms:
Payment will be made to the Bidder against the procured Goods and services according to the actual invoice or running bills submitted by the Bidder against the services provided within the time given in the conditions of the contract.
Number of GC Clause F
Identifying Defects:
The Authority reserves the right at any time to inspect the premises of the provider to inspect the goods and monitor the goods being provided.
A Standing Committee constituted by Chief Engineer (O&M) T&G FESCO Faisalabad vide his letter No.953 dated 02.06.2025 will witness the work done by the successful bidder and will issue a Inspection report to bidder comprising on the Tests carried out by the bidder within 48-Hours after repairing activity in the presence of standing committee. The bidder will submit this satisfactory Inspection Report while offering the Original Commercial Invoice.
The successful bidder will attend the oil leakage of the quoted quantities of Power Transformers energized at FESCO different Grid Stations against each LOT with in a period of 48-Hours from the start of shutdown applied by concerned Executive Engineer (SS&T) GSO FESCO at his own cost/expenses. The estimated time for the 100% completion of work is 60 days from the date of issuance of contract agreement.
In the event of delay in energization of 132/11.5KV, 31.5/40MVA, 20/26MVA, 10/13MVA Power Transformers and 66/11KV, 15/18MVA Power Transformer after due repair beyond 48-Hours from the completion of repair activity, the penalty @ 01% per day of the contract agreement value of Power Transformers subject to the maximum of 10% would be charged
Insulation Tests (IR and C&DF) must be done by the bidder before and after leakage repair activity.
During the time of currency of work order/rate contract if any amendment in specification is made by the competent Authority the contractor will be bound to repair the material according to amendments given by the authority without any extra cost/charges.
Bidder/Manufacturer/Supplier should have sufficient amount of leakage repair sealant/putty at the time of repair as the actual scope of leakage may increase due to various factors.
Bidder shall furnish a warranty certificate, certifying that the oil leakage repair of Power Transformers conform exactly to the specification laid down in the contract/ work and that in the event of the material being found defective or not confirming to the specification/particulars governing repair of the material and for a period of 18-months from the date of issuance of inspection report by the standing committee(continue)
you will be held responsible for all losses and the unacceptable goods shall be substituted with the acceptable goods at your expenses and cost.
100% payment of contractor’s bill excluding sales tax will be made by Superintending Engineer (GSO) FESCO Faisalabad through concerned Executive Engineer (SS&T) Divisions GSO FESCO on the receipt of the following documents along with bill in triplicate:-
Invoice/bill in triplicate.
Inspection Certificate/report issued by the standing committee.
Warranty Certificate.
Certificate to the effect that the billed amount has not been claimed or received earlier (Non-payment certificate).
Confirmation letter of acceptance of performance guarantee/security by the Chief Financial Officer FESCO Faisalabad.
Copy of sales tax invoice.
The amount of sales tax (if applicable) will be reimbursed by Superintending Engineer (GSO) FESCO Faisalabad through concerned Executive Engineer (SS&T) Divisions GSO FESCO Faisalabad as under:-
Sales Tax return cum payment challan.
Copy of Inspection Certificate/report issued by the standing committee.
Sales Tax Invoice.
In case the manufactures who pay lumpsum Sales Tax, they shall also submit an affidavit on non-judicial paper separately that “Challan includes the amount of Rs.___________of Sales Tax for repair of material to FESCO against P.O. No._______ dated._____________.
Number of GC Clause F 5 & 6
Following is the guidance for Dispute Resolution
Notwithstanding any reference to the arbitration herein, the parties shall continue to perform their respective obligations under the Contract unless they otherwise agree that the Authority shall pay the Bidder any monies due to the Bidder.
Arbitrator’s fee:
The fee shall be specified in Pak Rupees, as determined by the Arbitrator, which shall be shared equally by both parties.
Appointing Authority for Arbitrator:
By the Mutual Consent or in accordance with the provisions of Arbitration Act, 1940, in case the parties fail to reach a consensus on the name of sole arbitrator, any party may submit an application to the Chief Justice Islamabad High Court for appointment of sole arbitrator. The Chief Justice IHC may appoint a former judge of any High Court or Supreme Court as the sole arbitrator to resolve the dispute between the parties.
Rules of procedure for arbitration proceedings:
Any dispute between the Authority and a Bidder who is a national of the Islamic Republic of Pakistan arising in connection with the present Contract shall be referred to adjudication or arbitration in accordance with the laws of the Islamic Republic of Pakistan including Arbitration Act 1940, however above provision shall prevail in referring the case to the Arbitrator.
Place of Arbitration and Award:
The arbitration shall be conducted in English language and place of arbitration shall be at Islamabad. The award of the arbitrator shall be final and shall be binding on the parties.
Date: [insert date (as day, month and year)]
Bid No.:P145176
To: PMU (FESCO) (Faisalabad Electric Supply Company (FESCO)), Chief Engineer Chief Engineer (Development), FESCO Head Office, Canal Road, Faisalabad, Pakistan., Faisalabad City, Faisalabad (District), Faisalabad Division (Division), Punjab (Province).
We, the undersigned, declare that:
We understand that, according to your conditions, Bids must be supported by a Bid Securing Declaration.
We accept that we will be blacklisted and henceforth cross debarred for participating in respective category of public procurement proceedings for a period of (not more than) six months, if fail to abide with a bid securing declaration, however without indulging in corrupt and fraudulent practices, if we are in breach of our obligation(s) under the Bid conditions, because we:
We understand this Bid Securing Declaration shall expire if we are not the successful
Bidder, upon the earlier of (i) our receipt of your notification to us of the name of the successful Bidder; or (ii) twenty-eight (28) days after the expiration of our Bid.
THIS AGREEMENT made the _____ day of __________ 20_____ between PMU (FESCO) (Faisalabad Electric Supply Company (FESCO)), Chief Engineer Chief Engineer (Development), FESCO Head Office, Canal Road, Faisalabad, Pakistan., Faisalabad City, Faisalabad (District), Faisalabad Division (Division), Punjab (Province).
(hereinafter called “the Procuring Agency”) of the one part and [name of Bidder] of [city and country of Bidder] (hereinafter called “the Bidder”) of the other part:
WHEREAS the Procuring Agency invited Bids for provision of goods, viz., TENDER NO.NCB-881/FESCO/PMU/GSO/2026-27 FOR REPAIR OF 132/11.5KV, 31.5/40MVA POWER TRANSFORMERS, 132/11.5KV, 20/26MVA POWER TRANSFORMERS, 132/11.5KV, 10/13MVA POWER TRANSFORMERS AND 66/11KV, 15/18MVA POWER TRANSFORMERS (P145176) and has accepted a Bids by the Bidder for the provision of Goods in the sum of [contract price in words and figures] (hereinafter called “the Contract Price”).
NOW THIS CONTRACT WITNESSETH AS FOLLOWS:
1. In this Contract words and expressions shall have the same meanings as are respectively assigned to them in the Conditions of Contract referred to.
2. The following documents shall be deemed to form and be read and construed as part of this Contract, In the event of any ambiguity or conflict between the Contract Documents listed below, the order of precedence shall be the order in which the Contract Documents are listed below:-
3. In consideration of the payments to be made by the Procuring Agency to the Bidder as hereinafter mentioned, the Bidder hereby covenants with the Procuring Agency to provide the Goods related services and to remedy defects therein in conformity in all respects with the provisions of the Contract.
4. The Procuring Agency hereby covenants to pay the Bidder in consideration of the provision of Goods and the remedying of defects therein, the Contract Price or such other sum as may become payable under the provisions of the contract at the times and in the manner prescribed by the contract.
IN WITNESS whereof the parties hereto have caused this Contract to be executed in accordance with their respective laws the day and year first above written.
Signed, sealed, delivered by __________________the ________________ (for the Procuring Agency)
Witness to the signatures of the Procuring Agency:
………………………………………………
Signed, sealed, delivered by __________________the ________________ (for the Procuring Agency)
Witness to the signatures of the Bidder: …………………………………………………
Contract Number: Contract Value: Contract Title:
Dated:
[Name of Supplier] hereby declares that it has not obtained or induced the procurement of any contract, right, interest, privilege or other obligation or benefit from Government of Pakistan or any administrative subdivision or agency thereof or any other entity owned or controlled by it (GoP) through any corrupt business practice.
Without limiting the generality of the foregoing [Name of Supplier] represents and warrants that it has fully declared the brokerage, commission, fee etc. paid or payable to anyone and not given or agreed to give and shall not give or agree to give to anyone within or outside Pakistan either directly or indirectly through any natural or juridical person, including its affiliate, agent, associate, broker, consultant, director, promoter, shareholder, sponsor or subsidiary, any commission, gratification, bribe, finder's fee or kickback, whether described as consultations fee or otherwise, with the object of obtaining or inducing the procurement of a contract, right, interest, privilege or other obligation or benefit in whatsoever form from GoP, except that which has been expressly declared pursuant hereto.
[Name of Supplier] certifies that it has made and will make full disclosure of all agreements and arrangements with all persons in respect of or related to the transaction with GoP and has not taken any action or will not take any action to circumvent the above declaration, representative or warranty.
[Name of Supplier] accepts full responsibility and strict liability for making and false declaration, not making full disclosure, misrepresenting fact or taking any action likely to defeat the purpose of this declaration, representation and warranty. It agrees that any contract, right interest, privilege or other obligation or benefit obtained or procured as aforesaid shall, without prejudice to any other right and remedies available to GoP under any law, contract or other instrument, be voidable at the option of GoP.
Notwithstanding any rights and remedies exercised by GoP in this regard, [Name of Supplier] agrees to indemnify GoP for any loss or damage incurred by it on account of its corrupt business practices and further pay compensation to GoP in an amount equivalent to ten time the sum of any commission, gratification, bribe, finder's fee or kickback given by [Name of Supplier] as aforesaid for the purpose of obtaining or inducing the procurement of any contract, right, interest, privilege or other obligation or benefit in whatsoever form from GoP.
To: PMU (FESCO) (Faisalabad Electric Supply Company (FESCO)), Chief Engineer Chief Engineer (Development), FESCO Head Office, Canal Road, Faisalabad, Pakistan., Faisalabad City, Faisalabad (District), Faisalabad Division (Division), Punjab (Province).
WHEREAS [name of Bidder] (hereinafter called “the Bidder”) has undertaken, in pursuance of Contract No. [reference number of the contract] dated [insert date] for provision of Goods(hereinafter called “the Contract”).
AND WHEREAS it has been stipulated by you in the said Contract that the Bidder shall furnish you with a Bank Guarantee by a reputable bank for the sum specified therein as security for compliance with the Bidder’s performance obligations in accordance with the Contract.
AND WHEREAS we have agreed to give the Bidders guarantee:
THEREFORE, WE hereby affirm that we are Guarantors and responsible to you, on behalf of the Bidder, up to a total of [amount of the guarantee in words and figures], and we undertake to pay you, upon your first written demand declaring the Bidder to be in default under the Contract and without cavil or argument, any sum or sums within the limits of [amount of guarantee] as aforesaid, without your needing to prove or to show grounds or reasons for your demand or the sum specified therein.
This guarantee is valid until the: [insert date]
Signature and seal of the Guarantors
_____________________________________________________________________
[name of bank or financial institution]
_____________________________________________________________________
[address]
_____________________________________________________________________
[date}
Form must be Filled duly signed/stamped by the bidder.
To be awarded a contract for this order, the bidder has to have an average annual turnover in the last 3 years equal to one time of the quoted price.
Document must be uploaded duly signed & stamped by the bidder.